Product type | Actuator |
IP rating | IP54 |
Input Signal | 0..10 Vdc, MP-BUS |
Manufacturer | Belimo |
Power Supply | 24Vac/Vdc |
Torque | 20 Nm |
Running time | 140 to 150 sec |
Actuator type | Rotary |
Control Type | Modulating |
At IACS we provide Free Delivery and Next 1-2 day Delivery for all the Belimo Actuators in stock.
The Belimo SM24A-MP is an Actuator used in HVAC systems and applications to manage dampers.
This type of Actuator applies a Rotary motion to regulate the damper.
The Torque force applied by the SM24A-MP is 20 Nm.
The power supply requested for this Rotary Actuator is 24Vac/Vdc.
IACS has the best prices on the right Belimo Actuators for your system.
Consult the Belimo custom datasheet above or contact iacs via email for personalised assistance if you have queries about size or installation.
Features
• Electrical data Nominal voltage AC 24 V, 50/60 Hz / DC 24 V
• Nominal voltage range AC 19.2 ... 28.8 V / DC 21.6 ... 28.8 V
• Power consumption In operation 3.5 W @ nominal torque
• At rest 1.25 W
• For wire sizing 6 VA
• Connection Cable 1 m, 4 x 0.75 mm2
• Control Control signal Y 0 ... 20 mA, input impedance 500 Working range 4 ... 20 mA
• Position feedback (measuring voltage U) DC 2 ... 10 V, max. 0.5 mA
• Uni-rotation ±5%
• Functional data Torque (nominal torque) Min. 20 Nm @ nominal voltage
• Direction of rotation Can be selected with 0 / 1
• Manual override Disengaging the gearing latch by means of a pushbutton, self-resetting
• Angle of rotation Max. 95° , can be limited at both ends withadjustable mechanical end stops
• Running time 150 s / 90°<
• Sound power level Max. 35 dB (A)
• Position indication Mechanical, pluggable
• Automatic adjustment of running time, operating range and measuring signal U to match the mechanical angle of rotation Manual triggering of this adaption by
pressing the button «Adaption» or with the PC-Tool
• Direction of motion at Y = 0 V At switch position 0 resp. 1
• Protection class III Safety extra-low voltage
• Degree of protection IP54 in all mounting positions
• EMC CE according to 2004/108/EC
• Certification cULus according to UL 60730-1A and UL 60730-2-14 and CAN/CSA E60730-1:02 Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
• Mode of operation Type 1
• Rated impulse voltage 0.8 kV
• Control pollution degree 3
• Ambient temperature –30 ... +50°C
• Non-operating temperature –40 ... +80°C
• Ambient humidity 100% r.H.
• Maintenance Maintenance-free
• Dimensions / Weight
• Dimensions See «Dimensions» on page 5
• WeightApprox. 920 g