Product type | Actuator |
IP rating | IP54 |
Input Signal | On/Off |
Manufacturer | Belimo |
Power Supply | 24Vac/Vdc |
Torque | 2 Nm |
Running time | 65 to 80 sec |
Actuator type | Rotary |
At IACS we provide Free Delivery and Next 1-2 day Delivery for all the Belimo Actuators in stock.
The Belimo CM24-T-L is an Actuator used in HVAC systems and applications to manage dampers.
This type of Actuator applies a Rotary motion to regulate the damper.
The Torque force applied by the CM24-T-L is 2 Nm.
The power supply requested for this Rotary Actuator is 24Vac/Vdc.
Find at IACS the ideal Belimo Actuator compatible with your system at the best price.
If you are unsure about size or installation, refer to the Belimo custom datasheet above or message iacs to receive special instructions and a custom quote.
CM24-T-L Damper actuator 2 Nm, 75 s, 95° AC / DC 24 V, Open/Close
• Damper actuator
• 2 Nm, 75 s,
• AC / DC 24 V, Open/Close, 3-point
• IP 54, Manual override Gear disengagement with magnet
• Control with single- / 2-wire contact
• Connection PVC cable 1m
• Direction of rotation rotation to the right (cw)
• Spindle driver Clamp 6...12.7 mm
• Nominal voltage AC 24 V, 50/60 Hz / DC 24 V
• Nominal voltage range AC/DC 19.2 ... 28.8 V
• Power consumption In operation At rest For wire sizing 0.5 W @ nominal torque 0.2 W 1 VA
• Connection Terminals for 3 x 1.5 mm2 CU wire or 3 x 1.0 mm2 CU litz wires
• Functional data Torque (nominal torque) Min. 2 Nm @ nominal voltage
• Direction of rotation See «Type overview»
• Angle of rotation Without limit With limit Endless Fixed 315° or 0 ... 287.5° with mechanical end stops, can be adjusted in 2.5° increments
• Running time 75 s / 90°
• Sound power level Max. 35 dB (A)
• Position indicator Mechanical, pluggable (with integrated magnet for gear disengagement)
• Safety Protection class III Safety extra-low voltage / UL Class 2 Supply
• Degree of protection IP20 in any mounting position NEMA1, UL Enclosure Type 1
• EMC CE according to 2004/108/EC
• Certification cULus according to UL 60730-1A and UL 60730-2-14 and CAN/CSA E60730-1:02 Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
• Mode of operation Type 1 (EN 60730-1)
• Rated impulse voltage 0.8 kV (EN 60730-1)
• Control pollution degree 2 (EN 60730-1)
• Ambient temperature –30 ... +50°C
• Non-operating temperature –40 ... +80°C
• Ambient humidity 95% r.H., non-condensating (EN 60730-1)
• Maintenance – free